Case Study on Main Fan Selection and Application for a 1-Million-Ton-Per-Year Calcite Mine in Guangxi
Case study of a main mine fan for a million-tonne-scale calcite mine in Guangxi: Model FKCDZ-8-№23/2×132kW; airflow 48.9–117.1 m³/s; static pressure 499–2204 Pa; characterized by stable, energy-efficient operation and successful safety certification.
Case Details
Case Study on Main Fan Selection and Application for a 1-Million-Ton-Per-Year Calcite Mine in Guangxi
I. Background
Guangxi is a region rich in calcite resources, boasting proven reserves that rank among the highest in China. The ore is of excellent quality and is widely used in industries such as plastics, coatings, papermaking, and construction materials. With the continuous expansion of the downstream calcium carbonate industry, the scale of calcite mining in the region has grown year by year, and underground mines with an annual output of one million tons have gradually become the norm. Unlike small-scale mines, these million-ton-class mines feature complex underground roadway networks, dispersed mining faces, and numerous ventilation points. Consequently, the ventilation system must not only meet basic requirements—such as providing breathable air for personnel and diluting dust—but also supply sufficient airflow and pressure to exhaust emissions from mining equipment and clear blasting fumes.The mine utilizes an adit (horizontal tunnel) development method. The ore body is bedded, with stopes extending significantly along the strike, and mining levels are progressively deepening. After the mine commenced operations, capacity bottlenecks in the original ventilation system became apparent as mining progressed. There was an urgent need to install a main fan at the return air shaft capable of overcoming the mine's total ventilation resistance. Following ventilation network analysis and a comparison of options, the FKCDZ-8-№23/2×132kW mine-duty exhaust-type contra-rotating axial-flow fan was selected as the main fan. Its design specifications include an airflow range of 48.9–117.1 m³/s, a static pressure range of 499–2204 Pa, dual 132 kW motors, and a rotational speed of 730 rpm.
II. Challenges
The core challenges facing the mine's ventilation system can be understood at three levels.The first level involves the complex distribution of ventilation resistance. The calcite ore body is hosted within carbonate rock strata; while the surrounding rock of the roadways is generally stable, the presence of fault fracture zones and areas with developed karst fissures increases local ventilation resistance. As mining levels extend deeper and return-air routes lengthen, the total mine ventilation resistance increases non-linearly. Ventilation network analysis indicates that under the most demanding operating conditions, the total static pressure requirement approaches 2,200 Pa. Undersizing the fan leads to a chain reaction: insufficient airflow, rising temperatures at working faces, and dust accumulation. Conversely, oversizing results in the fan operating inefficiently for extended periods, causing significant energy waste.A second challenge lies in the significant fluctuation of operating conditions. For mines with an annual output of one million tonnes, the pace of mining and development turnover is rapid, resulting in marked differences in the number and location of active stopes across various production phases. During the infrastructure phase, there are numerous development faces and concentrated airflow demands; during full production, stopes are dispersed and airflow paths lengthen; and during deep-level development, return-air routes extend even further. Consequently, the main fan requires a broad high-efficiency operating range—maintaining reasonable efficiency across airflow rates of 49–117 m³/s and static pressures of 499–2,204 Pa—rather than simply performing well near a single design point.A third challenge involves safety and regulatory compliance. Under the *Safety Regulations for Metal and Non-metal Mines* (GB16423—2020), the main fan serves as the core power unit ensuring the stability of the mine ventilation system; it must be capable of timely switching during power supply failures to guarantee ventilation reliability. Furthermore, in accordance with the *Safety Inspection Specifications for Main Fan Systems in Metal and Non-metal Mines* (AQ 2054—2016), main fans must undergo periodic inspections of parameters such as airflow, pressure, efficiency, vibration, and bearing temperature rise, with continued operation contingent upon passing these inspections. Therefore, mines must factor inspectability, maintainability, and failover capabilities into the equipment selection process.
III. Strategies
To address these challenges, the core logic of the selection strategy is to "define the fan performance envelope based on ventilation network requirements and determine the technical route based on full-lifecycle costs."Regarding the fan type, the exhaust-style contra-rotating axial-flow fan represents a suitable choice. The mine employs a mechanical exhaust ventilation system: fresh air enters via an adit, while foul air is extracted to the surface through a return air shaft by a main fan—a method well-established in non-coal mines such as calcite operations. The FKCDZ series counter-rotating axial-flow fans are specifically designed for the ventilation needs of non-coal mines (e.g., gold, iron, copper, fluorite, and calcite). They can serve as either main or auxiliary fans and are suitable for multi-stage station ventilation systems involving the coordinated operation of multiple fans.Regarding performance matching, the model's parameters cover the resistance range of typical mine ventilation networks. Operating at 730 rpm, the FKCDZ-8-№23/2×132kW model offers an adjustable airflow range of 48.9–117.1 m³/s and a static pressure range of 499–2204 Pa. These fans feature twisted airfoil blades designed based on 3D flow theory, achieving a static pressure efficiency of 0.86—a high level for main fans in non-coal mining. Crucially, the performance curve remains relatively flat within the high-efficiency zone; this ensures that if mine resistance fluctuates due to the progression of mining and excavation, the fan continues to operate at high efficiency rather than rapidly dropping into a low-efficiency range.In terms of safety redundancy, the dual-motor counter-rotating structure provides inherent fault tolerance. The 2×132 kW configuration means the two stages of impellers are driven independently. Aligning with the AQ 2054 standard—which mandates requirements for backup motors and rapid replacement capabilities—this dual-motor design allows for partial ventilation capacity to be maintained via reduced-load operation in the event of a single-stage failure, thereby buying time for maintenance. Additionally, the FKCDZ series supports airflow reversal by reversing the fan rotation (with a reversal efficiency exceeding 60%) without requiring a separate reversal air duct, a feature of practical value in emergency situations.
IV. Implementation
The implementation process following the equipment's arrival at the mine comprises three key stages: precision installation, phased commissioning, and performance verification. A critical aspect of the installation process was ensuring an airtight seal at the interface between the air duct and the fan. Exhaust ventilation systems demand a high level of airtightness; any air leakage directly reduces the effective airflow reaching the underground workings. The installation team employed a rigid connection method—using flanges and sealing gaskets—at the junction of the fan inlet and the air duct, while also sealing cracks and gaps in the duct's inner walls with grout. The fan's direct-drive configuration eliminated the need for belt or long-shaft transmissions, thereby reducing system losses and minimizing the impact of foundation settlement on operations, which kept the installation complexity manageable.The commissioning phase followed a progressive approach: "individual no-load testing," "dual-unit coordinated operation," and "blade angle adjustment under load." First, the two motors underwent separate no-load test runs to monitor vibration, bearing temperatures, and current balance. Next, the dual-unit counter-rotating system was started, and airflow versus static pressure data were recorded across various operating points—ranging from fully open to gradually closed air duct damper positions. Based on the measured results, the blade installation angles were fine-tuned to ensure the fan's operating points fell within the high-efficiency range as much as possible. The entire commissioning process lasted approximately 72 hours, covering the full spectrum of operating conditions from minimum to maximum resistance.Performance verification was conducted in accordance with the inspection criteria of standard AQ 2054—2016, with deviations between measured data and design parameters kept within acceptable limits. The fan operated stably under maximum mine resistance conditions; the measured static pressure approached 2,200 Pa, the airflow met the requirements for all working faces, and both bearing temperature rise and vibration levels remained within standard limits.
V. Results
Following the commissioning of the FKCDZ-8-№23/2×132kW main ventilation fan, the mine's ventilation system achieved quantifiable improvements.Regarding ventilation capacity, the total airflow in the return air shaft increased from approximately 85 m³/s prior to the upgrade to over 110 m³/s. The effective airflow rate at various mining and excavation faces improved significantly, and the temperature and dust concentration in the underground working environment were effectively controlled. Regarding operational stability, the dual-motor redundant design with a contra-rotating structure allows the fan to maintain approximately 60% of its ventilation capacity even in the event of a single-stage failure; combined with backup motors and rapid switching mechanisms, the continuous reliability of the ventilation system is significantly enhanced. The fan is designed for a service life of 15 years and can operate safely and continuously for at least 12,000 hours before its first major overhaul.In terms of energy consumption, although the installed power of a single main fan reaches 264 kW, the fan's wide high-efficiency range and excellent operational matching result in an actual operating power lower than that of a single-stage axial-flow fan delivering the same airflow. Based on energy-saving data from variable-frequency drive (VFD) retrofits in similar non-coal mines, the coordinated control of blade angle fine-tuning and frequency optimization can reduce main fan energy consumption by approximately 10%. Estimating an annual operation of 8,000 hours for the mine's ventilation system, the annual electricity savings could reach 150,000 to 200,000 kWh.Regarding compliance, the initial safety inspection following the fan's commissioning confirmed that all indicators met the requirements of China's mine safety standard AQ 2054—2016; key parameters—such as airflow, air pressure, efficiency, vibration, and bearing temperature—were all within acceptable limits, enabling the mine to successfully pass the safety production standardization review.
VI. Insights
This case study offers several transferable lessons for the design of ventilation systems in non-metallic mines with million-tonne annual capacities.First, the core principle in selecting a main fan is not simply choosing the largest unit, but rather selecting one with a wide operating range. Mine ventilation requirements evolve throughout the mine's lifecycle; consequently, the width of the fan's high-efficiency range is more critical than its peak performance metrics. The FKCDZ series offers over 200 specifications through various combinations of hub ratios and motor pole counts, enabling excellent matching between the fan and the ventilation network. This selection approach is worthy of adoption by similar mines.Second, the requirements for fan airtightness and reverse-airflow capability inherent in exhaust-type ventilation systems should be factored into the assessment during the selection phase. While the "air reversal rate exceeding 40%" appears merely as a figure on a specification sheet, it is a critical factor determining the feasibility of rescue operations during emergencies such as underground fires.Thirdly, compliance with safety inspection standards must be addressed from the moment equipment arrives on-site. The AQ 2054—2016 standard outlines inspection criteria for main ventilation fan systems covering multiple parameters—such as inlet ducts or air drifts, braking mechanisms, motor output power, grounding resistance, insulation resistance, blade clearance, and bearing temperature—and the standard itself continues to undergo revision and refinement. By explicitly stipulating in procurement contracts that suppliers must assist with the initial safety inspection, mines can effectively prevent acceptance hurdles arising from technical documentation issues or installation defects.Fourthly, the potential for energy savings in a ventilation system often lies not in the fan unit itself, but in how well the fan is matched to the ventilation network. Experience from this mine demonstrates that fine-tuning blade angles based on actual operational data—shifting the operating point from a low-efficiency zone to a high-efficiency zone—can yield energy savings more directly and cost-effectively than replacing the equipment with a higher-efficiency model.